Аннотация:
Electrical breakdown strength of liquid–gas micro bubble mixtures of transformer oil with sulfur hexafluoride and air for the case of quasi homogeneous gas inclusions distribution and $10\%$ volumetric gas content was experimentally investigated. DC voltage up to $140$ kV was applied to a $8$ mm gap between hemispherical electrodes. It is shown that transformer oil bubbled with air leads to threshold breakdown voltage decrease by
$34\%$ and $19\%$ when bubbled with sulfur hexafluoride. The stabilization effect of sulfur hexafluoride micro bubbles on the value of threshold breakdown voltage is observed.