Abstract:
The effect of the rate of the rise in the current to 1700 A/ms on the characteristics of a transition of units of superconducting (HTSC) modules from a superconducting to normal state has been experimentally studied. The units differed by the critical current of the HTSC tape and design. The units of HTSC modules are used as a part of the resistive superconducting fault current limiter (SFCL) for ac and dc grids. The obtained dependences should be taken into account when designing a resistive SFCL.