RUS  ENG
Full version
JOURNALS // Pisma v Zhurnal Tekhnicheskoi Fiziki // Archive

Pisma v Zhurnal Tekhnicheskoi Fiziki, 2018 Volume 44, Issue 20, Pages 79–86 (Mi pjtf5669)

This article is cited in 8 papers

The influence of the mass flow rate on the critical heat flux during subcooled deionized water boiling in a microchannel cooling system

V. V. Kuznetsov, A. S. Shamirzaev

S.S. Kutateladze Institute of Thermophysics, Siberian Division of the Russian Academy of Sciences

Abstract: We have experimentally studied the influence of the mass flow rate on the critical heat flux (CHF) during the boiling of deionized water underheated relative to the saturation temperature in a microchannel cooling system. The experimental unit comprised a copper-based block with two 0.36-mm-deep microchannels of 2 mm width and 16 mm length. The mass flow rate ranged from 100 to 600 kg/(m$^2$ s) and the initial subcooling was varied from 30 to 70$^{\circ}$C. It was found that the character of boiling crisis changed with increasing mass flow rate and the CHF significantly increased upon complete condensation of vapor in the distribution chamber of the cooling system.

Received: 08.11.2017

DOI: 10.21883/PJTF.2018.20.46809.17114


 English version:
Technical Physics Letters, 2018, 44:10, 938–941